Power Frequency High Voltage Resonant Test System

EP HIPOT ELECTRIC CO., LTD.
  • After-sales Service:Onsite and Remote Guidance
  • Warranty:2 Years Free Warranty Longlife Service
  • Type:Transformer
  • Application:AC Hipot
  • Certification:CE, ISO9001: 2000, ISO, SGS
  • Condition:New

Base Info

  • Model NO.:EPCZ-560kVA , 40kV
  • Hv Reactor:Epdk- 70kVA,40kv (40kv,1.75A)
  • Exciting Transformer:Epcb- 50kVA,3kv,6kv
  • Variable Frequency Power Supply:Epcz-100kw,380V
  • Capacitive Divider:Epfr- 40kv,0.003UF (60kv)
  • Rated Output Voltage:0~40kv
  • Resonant Voltage Waveform:Sine Wave, Waveform Distortion Rate <1.0%
  • Maximum Tested Product Current:1.75A 14A
  • Maximum Test Capacity:560kVA
  • Output Frequency:30~300Hz
  • Working Time:Continuous Working Time Is 60min Under Full Power
  • Quality Factor:30~90
  • Input Working Power:Three-Phase 380V 5%, 50Hz
  • Ambient Temperature:-15c ~+40 C
  • Relative Humidity:<90rh%, No Condensation
  • Noise:Less Than 50dB
  • Transport Package:Plywood Case with Foam and Waterproof Plastics
  • Specification:Customized
  • Trademark:EP Hipot
  • Origin:Wuhan, China
  • HS Code:9030339000
  • Production Capacity:500,Year

Description

Basic Info.

Model NO. EPCZ-560kVA / 40kV Hv Reactor Epdk- 70kVA/40kv (40kv/1.75A) Exciting Transformer Epcb- 50kVA/3kv/6kv Variable Frequency Power Supply Epcz-100kw/380V Capacitive Divider Epfr- 40kv/0.003UF (60kv) Rated Output Voltage 0~40kv Resonant Voltage Waveform Sine Wave, Waveform Distortion Rate <1.0% Maximum Tested Product Current 1.75A 14A Maximum Test Capacity 560kVA Output Frequency 30~300Hz Working Time Continuous Working Time Is 60min Under Full Power Quality Factor 30~90 Input Working Power Three-Phase 380V 5%, 50Hz Ambient Temperature -15c ~+40 C Relative Humidity <90rh%, No Condensation Noise Less Than 50dB Transport Package Plywood Case with Foam and Waterproof Plastics Specification Customized Trademark EP Hipot Origin Wuhan, China HS Code 9030339000 Production Capacity 500/Year

Product Description

AC Resonance Test System EPCZ-560kVA / 40kV (can be applied on 100MW Generator and 10kV 35kV Cable)

The system is consisted by below units
  • Variable Frequency Power supply
  • Exciting Transformer
  • HV Reactor
  • Capacitive Divider
  • Accessories Carrycase (connection wires)
Working Environment
  • Environmental temperature: -15ºC to 40ºC
  • Related humidity: 90% RH
  • Altitude: 5000m

Application and requirement
  1. Meet the 15.6kV/1000MVA generator AC withstand voltage test, capacitance1.4uF, test frequency 45~65Hz, test voltage U34.8kV (2Un+3). Test time: 1 minute
  2. Meet 10kV/300mm2 cable AC withstand voltage test, capacitance1.12uF, test frequency 30~300Hz, test voltage U22kV. Test time: 5 minutes
  3. Meet 35kV/300mm2 cable AC withstand voltage test, capacitance0.398uF, test frequency 30~300Hz, test voltage U52kV. Test time: 60 minutes
  4. Meet the AC withstand voltage test of 10kV transformer, switch, etc., capacitance 0.0006uF, test frequency 30~300Hz, test voltage U35kV. Test time: 1 minute


System technical specifications
1 System technical data table
Rated output voltageRated output voltage: 0~40kV
Resonant voltage waveformsine wave, waveform distortion rate <1.0%
Maximum tested product current1.75A 14A
Maximum test capacity560kVA
Output frequency30~300Hz
Working timeContinuous working time is 60min under full power output
Quality factor30~90
Input working powerThree-phase 380V±5%, 50Hz
Ambient temperature-15ºC~+40ºC
Relative humidity<90RH%, no condensation
Altitude<5000m
Noise50dB

2 System performance characteristics
  1. Make full use of our company's advantages in electronic measurement technology and electromagnetic compatibility, completely independently develop, design and produce all components of this set of equipment including: variable frequency power supply, excitation transformer, cast high voltage reactor and high-precision capacitive voltage divider.
  2. Equipped with manual/automatic mode, large screen display, test parameter setting, and automatic timing and operation prompt functions.
  3. Possess multiple protection functions, such as: overvoltage, overcurrent protection, discharge protection, detuning protection, etc.

Device capacity determination
The capacity of the equipment is designed to be 560kVA/40kV divided into 8 reactors, and the single reactor is 40kV/1.75A/70H in combination to meet the test requirements of the above-mentioned tested product
.


Conclusion determination:1. 15.6kV/1000MW generator, electric capacity ≤1.4μF, test frequency 45-65Hz, test voltage 34.8kV.Use 8 reactors in parallel, at this time the inductance is L=70/8=8.6H
Test frequency f=1/2π√LC=1/(2×3.14×√8.6×1.4×10-6)=45.2Hz.
Test current I=2πfCUTest =2π×45.2×1.4×10-6×34.8×103=13.77A

When 8 reactors are used in parallel, the maximum current is 14A, so 14A>13.77A, this set of equipment can meet the requirements of the above tested product.

2. 15.6kV/10MW generator, electric capacity ≤0.1μF, test frequency 45-65Hz, test voltage 34.8kV.Use 1 reactor, at this time the inductance is L=70
Test frequency f=1/2π√LC=1/(2×3.14×√70×0.1×10-6)=60Hz.
Test current I=2πfCUTest =2π×60×0.1×10-6×34.8×103=1.15A

The maximum current of 1 reactor is 1.75A, so 1.75A>1.15A, this set of equipment can meet the requirements of the above tested product.

Conclusion: The device capacity is set to 560kVA/40kV, divided into 8 reactors, and the single reactor is 40/1.75A/70H in combination to meet the test requirements of the tested product.

More details on AC Resonance Test System EPCZ-560kVA / 40kV please contact EP Hipot Electric.
 